Bộ điều khiển Deepsea DSE7110
Bộ điều khiển Deepsea DSE7110 MKII - Auto Start Control Module
Hình ảnh bộ điều khiển Deepsea DSE7110
FEATURES
|
|
|
The DSE7110 MKll Auto Start
Control Module and the DSE7120 MKll Auto Mains (Utility) Failure Control Module are suitable for a wide variety of single gen-set applications. Monitoring engine speed, oil pressure, coolant temperature, frequency, voltage, current, power and fuel level, the modules will give comprehensive engine and alternator protection. This will be indicated on a large back-lit LCD icon display via an array of warning, electrical trip and shutdown alarms |
Electronic J1 939 (CAN) and nonelectronic MPU and alternator
sensing engine support for diesel, gas and petrol engines all in one variant. With a number of flexible inputs, outputs and protections, the modules can be easily adapted to suit a wide range of applications.
Compehensive power metering for
both generator and load is available (kW, kV A, kV Ar, pf). A real time clock allows scheduling while a 50 event log provides extensive event interrogation. |
Through USB Communication both
modules can be easily configured using the DSE Configuration Suite PC Software or can be fully configured through the module's front panel editor.
All DSE products are supported by
the DSE global technical support team which gives our customers and end users access to 24 hour system help and advice. |
KEY BENEFITS
• Automatically transfers between mains (utility) and generator (DSE71 20 MKll only) • Hours counter provides accurate information for monitoring and maintenance periods • User-friendly set-up and button layout for ease of use • Multiple parameters are monitored & displayed simultaneously • The module can be configured to suit a wide range of applications • Compatible with a wide range of CAN engines, including tier 4 engine support • Uses DSE Configuration Suite PC Software for simplified configuration • Licence-free PC software • IP65 rating (with supplied gasket) offers increased resistance to water ingress |
KEY FEATURES
• Large back-lit icon display • Heated display option available • Fully configurable via the fascia or PC using USB communication • Extremely efficient power save mode • 3 phase generator sensing • 3 phase mains (utility) sensing (DSE71 20 MKll only) • Generator/load power monitoring (kW, kV A, kV Ar, pf) • Generator overload protection (kW) • Generator/load current monitoring and protection • Fuel and start outputs (configurable when using CAN) • 4 configurable DC outputs • 2 configurable volt-free outputs • 4 configurable analogue/digital inputs • 6 configurable digital inputs • Support for 0-1 0 V & 4-20 mA oil pressure sensors |
• Configurable staged loading
outputs • CAN, MPU and alternator speed sensing in one variant • 3 engine maintainance alarms • Engine speed protection • Engine hours counter • Engine pre-heat • Engine run-time scheduler • Engine idle control for starting & stopping • Battery voltage monitoring • Start on low battery voltage • Real time clock • Fuel pump control • Configurable remote start input • 1 alternative configuration • Comprehensive warning, electrical trip or shutdown protection upon fault condition • LCD and LED alarm indication • Event log (50) |
SPECIFICATION
|
|
|
DC SUPPLY
CONTINUOUS VOLTAGE RATING 8 V to 35 V Continuous CRANKING DROPOUTS Able to survive 0 V for 50 mS, providing supply was at least 1 0 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking. MAXIMUM OPERATING CURRENT 290 mA at 1 2 V, 1 40 mA at 24 V MAXIMUM STANDBY CURRENT 75 mA at 1 2 V, 40 mA at 24 V CHARGE FAIL/EXCITATION RANGE 0 V to 35 V GENERATOR & MAINS (UTILITY) VOLTAGE RANGE 1 5 V to 41 5 V AC (Ph to N) 26 V to 71 9 V AC (Ph to Ph) |
FREQUENCY RANGE
3.5 Hz to 75 Hz MAGNETIC PICKUP VOLTAGE RANGE +/- 0.5 V to 70 V FREQUENCY RANGE 1 0,000 Hz (max) INPUTS DIGITAL INPUTS A TO F Negative switching ANALOGUE INPUTS A TO C Configurable as: Negative switching digital input 0 Ω to 480 Ω ANALOGUE INPUT D Configurable as: Negative switching digital input 0 V to 1 0 V 4 mA to 20 mA 0 Ω to 480 Ω |
OUTPUTS
OUTPUT A & B (FUEL & START) 1 0 A short term, 5 A continuous, at supply voltage OUTPUTS C & D 8 A AC at 250 V AC (Volt-free) AUXILIARY OUTPUTS E, F, G & H 2 A DC at supply voltage DIMENSIONS OVERALL 240 mm x 1 81 mm x 42 mm 9.4” x 7.1 ” x 1 .6” PANEL CUT-OUT 220 mm x 1 60 mm 8.7” x 6.3” MAXIMUM PANEL THICKNESS 8 mm 0.3” STORAGE TEMPERATURE RANGE -40 °C to +85 °C -40 °F to +1 85 °F OPERATING TEMPERATURE RANGE -30 °C to +70 °C -22 °F to +1 58 °F HEATED DISPLAY VARIANT -40 °C to +70 °C -40 °F to +1 58 °F |